Seismic checks - Columns (Seismic: AISC 341)

Tekla Structural Designer
2021
Tekla Structural Designer

Seismic checks - Columns (Seismic: AISC 341)

Classification

In all cases if the given “width to thickness ratio” is less than or equal to the given limit, then the seismic classification is satisfied.

AISC 341-16 and AISC 341-10

Columns in OMF and OCBF – No additional requirements.

Columns in IMF – Columns must satisfy the requirements of clause D1.1b for “moderately ductile” members.

Columns in SMF and SCBF – Columns must satisfy the requirements of clause D1.1b for “highly ductile” members.

The loading conditions affect the seismic classification in the following way,

  • Axial tension only – no classification required.
  • Any other loading condition – the appropriate rules in the section classification table are applied.

See: AISC 341-16 and AISC 341-10 seismic classification - all members

AISC 341-05

Columns in OMF and OCBF – No additional requirements.

Columns in IMF – Columns must satisfy clause 8.2a i.e. the requirements for Compact sections to AISC 360-05 in Table B4.1.

Columns in SMF and SCBF – Columns must satisfy Clause 8.2b for “seismically compact” sections.

The loading conditions affect the seismic classification in the following way,

  • Axial tension – no classification required.
  • Any other loading condition – the appropriate rules in the section classification table are applied.

See: AISC 341-05 seismic classification - all members

AISC 341-16, D1.4a Required strength

This check consists of two analyzes of the column - one that uses the 'amplified seismic load' and a second that uses a 'capacity analysis' as an upper bound. The moments and shears in the column are ignored and the column is designed for axial load only.

Note: While applying the column strength requirements of D1.4a, it is assumed that there are no loads applied to the column between locations of lateral support. Therefore applied moments are ignored and only the axial strength is considered as permitted in AISC 341-10 D1.4a(2).
Note: While applying the column strength requirements of D1.4a (2), the upper limit on the required strength with respect to overturning uplift as per D1.4a (2) (b) is not applied.

Overstrength seismic load

Pamp, the required axial strength (either tension or compression) including the “overstrength seismic load” is given by,

Pamp = Pr + fE/ρ * PE * (Ωo - ρ)

Where;

Pr = the axial force (-ve for tension and +ve for compression) determined from the analysis of the seismic load combination (LRFD or ASD). This may be the result of a first or second order analysis.

PE = the axial force (-ve for tension and +ve for compression) determined from the analysis of the seismic loadcase(s) associated with the seismic load combination.

fE = the strength load factor associated with the seismic load in the seismic load combination (base combination factor x ρ) (for example, 0.683 in the ASD combination, D + 0.75 L + 0.75 Lr + 0.683 E).

ρ = the redundancy factor, ρ1 when the column is assigned to Direction 1 and r2 when the column is assigned to Direction 2 (from the Seismic Wizard).

Ωo = the overstrength factor, Ωo1 when the column is assigned to Direction 1 and Ωo2 when the column is assigned to Direction 2 (from the Seismic Wizard...).

Note: The axial force from the load combination including the amplified seismic loads is calculated by swapping out the component due to the seismic loadcase Eh = ρ QE and replacing it with the amplified seismic load, Emh = ΩE QE.

Design condition

For each stack, the required axial strength, Pr is compared with the nominal axial strength, Pn, i.e. the design condition is,

Pr ≤ ɸ x Pn (LRFD) or Pn/Ω (ASD)

Where

Pn = the nominal axial strength in tension or compression as appropriate to the sign of Pr

ɸ = the resistance factor for tension or compression as appropriate

Ω = the safety factor for tension or compression as appropriate

AISC 341-10, D1.4a Required strength

This check consists of two analyzes of the column - one that uses the 'amplified seismic load' and a second that uses a 'capacity analysis' as an upper bound. The moments and shears in the column are ignored and the column is designed for axial load only.

Note: While applying the column strength requirements of D1.4a, it is assumed that there are no loads applied to the column between locations of lateral support. Therefore applied moments are ignored and only the axial strength is considered as permitted in AISC 341-10 D1.4a(2).
Note: While applying the column strength requirements of D1.4a (2), the upper limit on the required strength with respect to overturning uplift as per D1.4a (2) (b) is not applied.

Amplified seismic load

Pamp, the required axial strength (either tension or compression) including the “amplified seismic load” is given by,

Pamp = Pr + fE/ρ * PE * (Ωo - ρ)

Where;

Pr = the axial force (-ve for tension and +ve for compression) determined from the analysis of the seismic load combination (LRFD or ASD). This may be the result of a first or second order analysis.

PE = the axial force (-ve for tension and +ve for compression) determined from the analysis of the seismic loadcase(s) associated with the seismic load combination.

fE = the strength load factor associated with the seismic load in the seismic load combination (base combination factor x ρ) (for example, 0.683 in the ASD combination, D + 0.75 L + 0.75 Lr + 0.683 E).

ρ = the redundancy factor, ρ1 when the column is assigned to Direction 1 and r2 when the column is assigned to Direction 2 (from the Seismic Wizard).

Ωo = the overstrength factor, Ωo1 when the column is assigned to Direction 1 and Ωo2 when the column is assigned to Direction 2 (from the Seismic Wizard...).

Note: The axial force from the load combination including the amplified seismic loads is calculated by swapping out the component due to the seismic loadcase Eh = ρ QE and replacing it with the amplified seismic load, Emh = ΩE QE.

Capacity analysis

At any level on a column there can be SFRS members and non-SFRS members. The principle of this check is that the former might be operating at their “capacity” in an earthquake and so they are likely to apply more force to the column than the global analysis would indicate. “Capacity” in this context also includes the possibility that the material is stronger than its specified yield (typical).

The capacity calculation involves establishing the capacities of the incoming SFRS members at each node (level) in the column – these might be zero if there are only non-SFRS members at that level. The capacities so determined are then resolved into the local x-axis of the column. The capacities are calculated for beams and braces only, not the columns themselves.

The end result of the capacity analysis is that for each stack there is an axial force, Pcap which can be compression or tension. This will be included in the results and used in this design check to D1.4a but will only govern if smaller than that from the “Amplified seismic load” analysis.

Design condition

For each stack, the required axial strength, Pr (the smaller of Pcap or Pamp) is compared with the nominal axial strength, Pn, i.e. the design condition is,

Pr ≤ ɸ x Pn (LRFD) or Pn/Ω (ASD)

Where

Pn = the nominal axial strength in tension or compression as appropriate to the sign of Pr

ɸ = the resistance factor for tension or compression as appropriate

Ω = the safety factor for tension or compression as appropriate

AISC 341-16 and -10, E3.4a Moment ratio

At each level in a column where an SMF beam connects into the strong axis of the column (i.e. into the flange), a check is performed for each seismic combination to ensure that the plastic moment capacity of the column is greater than the plastic moment capacity of the incoming beams.

The design condition is,

∑ Mpcol / ∑ Mpbeam > 1.0

Note: The exceptions in E3.4a (a) and (b) are ignored and the check is performed for all SMFs.
Note: Beam column connections are always assumed braced as per E3.4c (1)
Note: All beams with pinned connections are excluded in this calculation. Any beam with a moment connection into the web of the column is ignored even if they are assigned to a SMF. On the other hand, any beam with a moment connection to the column flange is included in the calculation even if they are not assigned to a SMF.
Note: The additional moment due to shear amplification from the location of the plastic hinge to the column centre line (Muv and Mav) is calculated from two components,
  1. the shear inferred by the moment at the plastic hinge position based on the expected flexural strength of the beam,
  2. the shear force in the beam at the plastic hinge position from the factored gravity loads in the current seismic combination.
No account of angle of incoming members is taken into account in this calculation.)

AISC 341-16 and -10, F2.3 Analysis

This check applies to SCBF type frames only, the procedure being similar to that for 'Column Strength' to D1.4a.

Note: The approach taken to the “capacity analysis” per F2.3 assumes that the SCBF is reasonably isolated. That is, the influence of the remainder of the structure due to the braces operating at their capacity does not adversely affect the required strength.

Design condition

Moments in the column are permitted to be ignored as per F2.3 (1) and so only the axial check (compression or tension) is required.

For each stack, the required axial strength, Pr, is compared with the nominal axial strength, Pn, i.e. the design condition is,

Pr ≤ ɸ x Pn (LRFD) or Pn/Ω (ASD)

Where Pr = the required axial strength, Pcap

Pn = the nominal axial strength in tension or compression as appropriate to the sign of Pr

ɸ = the resistance factor for tension or compression as appropriate

Ω = the safety factor for tension or compression as appropriate

Note: While applying the column strength requirements of F2.3 (i) and (ii), it is assumed that there are no loads applied to the column between locations of lateral support. Therefore applied moments are ignored and only the axial strength is considered as permitted in AISC 341-10 F2.3 (1).
Note: While applying the column strength requirements of F2.3 (i) and (ii), the upper limits on the required strength per F2.3 (2) (a), (b) and (c) are not applied.
Note: It is assumed that braces do not carry significant gravity forces and therefore a separate analysis with braces omitted, in order to enhance the column gravity forces, is not carried out. [Ref. NEHRP Seismic Design Technical Brief No. 8].

AISC 341-05, 8.3 Required strength

The calculations for this check are exactly the same as those for the AISC 341-10, D1.4a Required Strength check except that they are only performed when the required axial force exceeds a certain limit as described below.

Pr > 0.4 x ɸc x Pn (LRFD)

Pr > 0.4 x Pn / Ωc (ASD)

Where

ɸc = 0.90

Ωc = 1.67

Pn = the nominal axial strength of the stack in compression or tension as appropriate to the sign of Pr

Either,

Pr = Pu

= the maximum axial force in the stack from the current (LRFD) seismic combination

Or,

Pr = Pa

= the maximum axial force in the stack from the current (ASD) seismic combination

Note: While applying the column strength requirements of 8.3, the upper limit on the required strength with respect to overturning uplift as per 8.3 (2) (b) is not applied.

AISC 341-05, 9.6 Moment ratio

At each level in a column where an SMF beam connects into the strong axis of the column (i.e. into the flange), a check is made to ensure that for each seismic combination the plastic moment capacity of the column is greater than the plastic moment capacity of the incoming beams. The calculations for this check are exactly the same as those for the AISC 341-10, E3.4a Moment Ratio check.

Note: The exceptions in 9.6 (a) and (b) are ignored and the check is performed for all SMFs.
Note: All beams with pinned connections are excluded in this calculation. Any beam with a moment connection into the web of the column is ignored even if they are assigned to a SMF. On the other hand, any beam with a moment connection to the column flange is included in the calculation even if they are not assigned to a SMF.
Note: The additional moment due to shear amplification from the location of the plastic hinge to the column centre line (Muv and Mav) is calculated from two components,

(i) the shear inferred by the moment at the plastic hinge position based on the expected flexural strength of the beam,

(ii) the shear force in the beam at the plastic hinge position from the factored gravity loads in the current seismic combination. No account of angle of incoming members is taken into account in this calculation.