How are EHFs used in Tekla Structural Designer and what for?

Tekla Structural Designer
Not version-specific
Tekla Structural Designer
EHF
sway
practical imperfections
alphacrit
1/200
Environment
British Standard
Eurocode

Introduction

Equivalent Horizontal Forces (EHF's) are used in two distinct and separate areas:

  1. Sway assessment and Second-order effects using the force amplification method.
  2. To make an allowance for Practical imperfections

     


These are not the same thing and should not be confused.


 

1. Why is the formula shown in the screenshot below used instead of the code equation 5.2 ?

See below under the title Sway

 

Image
EHF eq1

 

2. Sway

Any convenient set of lateral forces can be used to estimate the lowest elastic critical buckling load factor of a structure.  Whether this is called alpha_crit or lambda_crit or something else, it is essentially the same thing, and the method is a general one of structural theory, not unique to a particular design code. British Standards uses the same forces as those used for imperfections purely because they are already ‘to hand’ as it were, and this removes the necessity to calculate others.   Tekla Structural Designer adopts this method for the Eurocode for the same reasons.

Hence in Tekla Structural Designer for the Eurocode, the force used for the horizontal load is 0.5% which is the basic value of  = 1/200 stated in clause 5.3.2(3).

 

 

Image
EHF question

 


Because the horizontal load used to determine the sway deflections is always 0.5% of the total vertical load and 0.5% = 1/200, thus:

 

 

Image
Comparison


So when looking at sway it ends up as the same formula as BS:
 

Image
alpha crit

 

Should the deflections from Wind loads be considered in calculating sway for combinations including Wind?

Consider - if additional lateral loads are included in calculating the sway deflection, then Hed is increased and so is δ in direct proportion.  Hence the value of (HEd/δ ) remains unchanged as do h and Ved  .   Thus, there is zero total effect on the value of αcr.

Furthermore, the ‘original’ EC3 equation - using sway and (Hed/Ved ) calculated from ALL loads in the combination, including horizontal wind AND EHF’s - suffers from the same limitations as applying only EHF’s applied in isolation - i.e. it is no better - when buildings are not orientated in X/Y or the building itself has no clear set of orthogonal axes.  In addition, it suffers from the following additional issues:

 

  • The horizontal loads themselves may not be in the same direction as each other e.g. wind at 45 deg and NHF at 90 deg
  • The gravity loads can cause sway deflections that may increase or decrease the deflection due to the horizontal loads
  • Storey shears (HEd) do not make much sense when the floors are not readily identifiable or are sloping,
  • For a pure gravity load combination the horizontal load would be zero and the horizontal deflection could be zero making acr both zero and infinity!

     

Hence and in conclusion; the method discussed above is used in Tekla Structural Designer, since using the more complex code equation is no more ‘correct’, gives no benefit or greater accuracy and has additional drawbacks in the context of more “real-world” structures (in contrast to the very limited and simple structures/ load conditions considered in worked examples).

 

3. Practical Imperfections

In Eurocode  - in contrast to BS - practical imperfections are now included in all combinations, i.e. those that include other lateral loads and not just gravity.  Hence a reduction can be applied to these EHFs, when considering imperfections (not sway!), since other lateral load is already acting.  This is controlled via the settings shown in the screenshot below.

 

Image
EHF

 


This reduction is not applied to the EHF’s used in the sway assessment discussed above, as the factor of (1/200) used in the equation would also have to be adjusted by the same amount, and the effect would in any case cancel out.

 

Esta informação foi útil?