Verification Example - Wood Shear Wall Design - Perforated - Seismic (ASD)

Tekla Tedds
変更済み: 7 5月 2025
2026
Tekla Tedds Tekla Tedds for Word

Verification Example - Wood Shear Wall Design - Perforated - Seismic (ASD)

Description

This verification example utilizes Tekla Tedds to check a perforated wood shear wall for in-plane load due to seismic. This example is based on Design Example E3.4 of 2015/2018 Structural Wood Design Examples by American Wood Council (AWC) (pages 119 to 121). Comparisons and contrasts are tabularized and discussed regarding the results from Tedds and the AWC Design Example. The Tedds file used in this example is provided in the Tedds “Select Calculation” window, under Verification Examples.

Problem statement

Design the first-floor wall shown in Figure 1 as a perforated shear wall for a two-story house using Allowable Stress Design (ASD) provisions.

References

2015/2018 Structural Wood Design Examples by American Wood Council

2018 National Design Specification for Wood Construction

2015 Special Design Provisions for Wind and Seismic (SDPWS)

ASCE 7-10 Minimum Design Loads for Buildings and Other Structures

Example information

Seismic Design Category D1 (Based on 2015 International Residential Code (IRC))

 

Building Dimensions:

L = 40’

W = 32’

Roof pitch = 7:12

Top plate to ridge height = 9.3’

Wall height = 9’

Door height = 7’-6”

Window height = 4’-6”

Stud spacing = 16” o.c.

Studs: Southern Pine (G=0.55)

 

Applied shear load due to seismic force, Vs = 4,733 lbs (factored) (provided in AWC design example). Seismic load = 4,733 / 0.7 = 6,761 lbs is used in Tedds to account for the 0.7E factor in the ASCE 7-10 load combination.

 

Exterior wood sheathing: 7/16” thick Wood Structural Panel (WSP) Sheathing, 8d nails @ 4”o.c. edge spacing.

 

Interior sheathing: none

Notes / Assumptions

  • Deflection is not checked.

  • Chords are not designed in the AWS design example, but (3) 2x4 chords are provided within the shear wall.

  • It is assumed that the shear wall will occur in Dry conditions with a temperature of 100℉ or less.

  • A vertical anchor stiffness of 25,170 lb/in is used which correlates with a Simpson Strong-Tie HDU2-SDS2.5 holdown with an allowable tension load of 3,075 lbs.

  • Self-weight of the panel is not included in the AWC design example. A value of 1 psf was used in Tedds for the self-weight of the panel since Tedds does not allow a wall self-weight equal to 0 psf.

  • Holdown would need to be combined with 2nd floor holdown requirements, not included in the AWC design example or Tedds example.

Figure 1: Wood shear wall configuration

Comparison of Results between Tedds and AWC Design Example E3.4
Component Tedds Result AWC Design Example E3.4 % Difference
Design without interior Gypsum Wallboard
Maximum aspect ratio (based on WPS, per SDPWS 4.3.4) 3.5:1 3.5:1 0.0%
Largest aspect ratio in shear wall 3:1 3:1 0.0%
WSP nominal capacity (Seismic) 760 lb/ft 760 lb/ft 0.0%
ASD shear wall capacity (Seismic) 380 lb/ft 380 lb/ft 0.0%
Sum of perforated shear wall lengths (Li) 18' 18' 0.0%
Shear capacity adjustment factor (Co) 0.784 0.78 0.0%
Shear capacity (Seismic) 5,365 lbs

5,335 lbs

(380 lb/ft * 0.78 * 18’)

0.6%
Required holdown capacity, T 3,017 lbs

3,034 lbs

(4733 lb * 9’ / (0.78 * 18’))

0.6%

Conclusion

Upon reviewing the results above, the determination of shear wall capacity and holdown force for a perforated wood shear wall for seismic shear forces using Tekla Tedds is consistent with AWC Design Example 3.4, which references SDPWS. Users should feel confident that results determined in the Tedds Wood Shear Wall Design module are in agreement with NDS and SDPWS.