Verification Example - Axial Compression of Wood Column (ASD)

Tekla Tedds
Modified: 10 Mar 2026
2026
Tekla Tedds Tekla Tedds for Word

Verification Example - Axial Compression of Wood Column (ASD)

Description

This verification example utilizes Tekla Tedds to check the capacity of two interior wood columns with concentric compression loads. This example is based on Design Example E1.4 of 2015/2018 Structural Wood Design Examples by American Wood Council (AWC) (pages 23 to 27). Comparisons and contrasts are tabularized and discussed regarding the results from Tedds and the AWC Design Example. The Tedds file used in this example is provided in the Tedds “Select Calculation” window, under Verification Examples.

Problem statement

Compare the axial compression capacity of a nominal 4x4 and nominal 6x6 post being used for an interior column (only carrying gravity loads - dead load (DL) + floor live load (LL)). Both members are No. 2 Southern Pine and have a length of 10 feet. Both ends are assumed to be pinned (Ke = 1.0 - NDS 3.7.1.2). Assume all members are loaded concentrically.

References

2015/2018 Structural Wood Design Examples by American Wood Council

2018 National Design Specification for Wood Construction

Tedds calculation

Wood member design (NDS 2018) - Compared using version 2.2.29

Example information

Wood column information:

Sizes: 4x4 (nominal) and 6x6 (nominal)

Species: Southern Pine No. 2

Bearing length = 6”

Unbraced length - major and minor axis = 10’-0”

Buckling length factor - major and minor axis, Ke = 1.0

 

Reference and Adjusted Design Values:

4x4 post

Fc = 1,450 psi

E = E’ = 1,400,000 psi

Emin = E’min = 510,000 psi

 

6x6 post

Fc = 525 psi

E = E’ = 1,200,000 psi

Emin = E’min = 440,000 psi

 

CD = 1.0

CM = 1.0

Ct = 1.0

CT = 1.0

Ci = 1.0

CF = 1.0

Comparison of Results between Tedds and AWC Design Example E1.4
4x4 Wood Column
Component Tedds Result AWC Design Example E1.4 % Difference
Reference compression design value, Fc* 1,450 psi 1,450 psi 0.0%
Critical buckling design value, FcE 357 psi 357 psi 0.0%
Column stability factor, CP 0.232 0.232 0.0%
Adjusted compression stress, Fc 336 psi 336 psi 0.0%
Design axial compression force, P 4,120 lbs 4,120 lbs 0.0%
6x6 Wood Column
Component Tedds Result AWC Design Example E1.4 % Difference
Reference compression design value, Fc* 525 psi 525 psi 0.0%
Critical buckling design value, FcE 760 psi 760 psi 0.0%
Column stability factor, CP 0.801 0.801 0.0%
Adjusted compression stress, Fc 421 psi 421 psi 0.0%
Design axial compression force, P 12,725 lbs 12,725 lbs 0.0%

Conclusion:

Upon reviewing the results above, the axial capacities of 4x4 and 6x6 wood columns using Tekla Tedds are consistent with the results of AWC Design Example E1.4. Users should feel confident that results determined in the Tedds Wood Member Design module are in agreement with NDS.