Design parameters for shear (concrete column: EC2)
For some of the shear design parameters, additional user defined limits can be applied - where this is the case minimum and maximum values are specified in Design Settings > Concrete > Cast-in-place > Column > Reinforcement Layout. These are considered in addition to the EC2 or NA recommendations.
Minimum Shear Link Diameter
φw,min = MAX[ 6mm, 0.25 * largest longitudinal bar diameter ]
Maximum Span Region Shear Link Spacing
-
For design to UK NA, Irish NA, Malaysian NA and Singapore NA: 1
φw,max = MIN[ 20 * smallest longitudinal bar diameter, lesser column dimension, 400mm ]
Note:For UK NA when concrete class > C50/60 there are separate calculations in clause 9.5.3(3). These are not implemented but a warning is displayed in this situation.
-
For design to EC2 Recommendations:, Swedish NA
φw,max = MIN[ 20 * smallest longitudinal bar diameter, lesser column dimension, 400mm ]
-
For design to Finnish NA and Norwegian NA:
φw,max = MIN[ 15 * smallest longitudinal bar diameter, lesser column dimension, 400mm ]
Note that in the Norwegian NAthis limit is reduced by a factor of 0.6 for strength classes equal or above C55/67.
Support Region Shear Link Spacing
For support regions, the maximum link spacing is reduced by 40%. 2
Long Term Compressive Strength Factor for Shear
-
For design to EC2 Recommendations, UK NA, Irish NA, Malaysian NA, Singapore NA and Swedish NA: 3
αccw = 1.0
-
For design to Finnish NA and Norwegian NA:
αccw = 0.85
Design Concrete Compressive Strength for Shear
-
For design to UK NA, Irish NA, Malaysian NA and Singapore NA:
fcwd = αccw * MIN (fck , 50) /γC
-
For design to EC2 Recommendations, Finnish NA, Norwegian NA and Swedish NA:
fcwd = αccw * fck /γC
-
For design to EC2 Recommendations, UK NA, Irish NA, Malaysian NA, Singapore NA, Finnish NA and Swedish NA:
CRd,c = 0.18 / γC
-
For design to Norwegian NA:
CRd,c = 0.15 / γC
-
For design to EC2 Recommendations, UK NA, Irish NA, Malaysian NA, Singapore NA, Finnish NA and Swedish NA:
k1 = 0.15
-
For design to Norwegian NA:
If σcp ≥ 0, then k1 = 0.15, Else 0.30
Cracked Concrete Reduction Factor, v
-
For design to EC2 Recommendations, UK NA, Irish NA, Malaysian NA, Singapore NA, Finnish NA, Norwegian NA and Swedish NA: 6
v = 0.6 * (1 - (fck / 250))
Cracked Concrete Reduction Factor, v1
-
For design to UK NA: 7
v1 = v* (1 - (0.5 * cos(α))
α is the inclination of links.
Note that links in columns are always assumed to be at 90° to column direction.
Therefore v1 = v
-
For design to EC2 Recommendations, Irish NA, Malaysian NA, Singapore NA, Finnish NA, Norwegian NA and Swedish NA:
v1 = v
Minimum Shear Reinforcement Ratio
-
For design to EC2 Recommendations, UK NA, Irish NA, Malaysian NA, Singapore NA, Finnish NA, and Swedish NA:: 8
ρw,min = 0.08 * √(fck) / fyk
-
For design to Norwegian NA:
ρw,min = 0.1 * √(fck) / fyk
Maximum Angle of Compression Strut
-
For design to EC2 Recommendations, UK NA, Irish NA, Malaysian NA, Singapore NA, Finnish NA, Norwegian NA and Swedish NA: 9
cot(θmax) = 1
θmax = 45°
Minimum Angle of Compression Strut
-
For design to EC2 Recommendations, UK NA, Irish NA, Malaysian NA and Singapore NA:10
cot(θmin) = 2.5
θmin = 21.8°
-
For design to Norwegian NA:
If σt = NEd/Ac < fctk, 0,05
cot(θmin) = 2.5
θmin = 21.8°
else
cot(θmin) = 1.25
θmin = 38.7°
Angle of Compression Strut
-
For design to UK NA: 11
If NEd ≥ 0 i.e. compression
θ = 0.5 * arcsin(2 * vEd / (0.9 * αcw * v1 * fcwd))
else
cot(θ) = 1.25
θ = 38.7°
-
For design to EC2 Recommendations, Finnish NA, Norwegian NA and Swedish NA:
θ = 0.5 * arcsin(2 * vEd / (0.9 * αcw * v1 * fcwd))
-
For design to Irish NA, Malaysian NA and Singapore NA:
If NEd ≥ 0 i.e. compression
θ = 0.5 * arcsin(2 * vEd / (0.9 * αcw * v1 * fcwd))
else
cot(θ) = 1.00
θ = 45°
Stress State Factor
-
For design to EC2 Recommendations, UK NA, Irish NA, Malaysian NA, Singapore NA, Finnish NA, Norwegian NA and Swedish NA:
If σcp ≤ 0
αcw = 1.0
else if 0 < σcp ≤ 0.25 * fcd
αcw = 1.0 + (σcp / fcd)
else if 0.25 * fcd < σcp ≤ 0.5 * fcd
αcw = 1.25
else if 0.5 * fcd < σcp ≤ fcd
αcw = 2.5 * (1.0 - (σcp / fcd))
Minimum Shear Strength
-
For design to EC2 Recommendations, UK NA, Irish NA, Malaysian NA, Singapore NA, Finnish NA and Swedish NA: 12
vmin = 0.035 * k1.5 * fck 0.5
-
For design to Norwegian NA:
vmin = 0.035 * k2/3 * min(fck, 0.65)0.5