Classification (Beams: EC3 Eurocode)
General
The classification of the cross section is in accordance with EC3 Cl. 5.5 Table 5.2
A steel non-composite beam can be classified as:
-
Plastic Class = 1
-
Compact Class = 2
-
Semi-compact Class = 3
-
Slender Class = 4
Class 4 sections are unacceptable and are either failed in check mode or rejected in design mode.
Implementation of the below clauses is as follows:
-
Classification is determined using clause 5.5.2 (6) and not 5.5.2 (7).
-
Clause 5.5.2 (9) is not implemented as clause (10) asks for the full classification to be used for buckling resistance.
-
Clause 5.5.2 (11) is not implemented.
-
Clause 5.5.2 (12) is not implemented.
The note at the end of clause 5.5.2 is not implemented. A brief study by CSC (UK) Ltd of UK rolled UBs and UCs showed that flange induced buckling in normal rolled sections is not a concern. No study was undertaken for plated sections.
Hollow sections
The classification rules for SHS and RHS relate to “hot-finished hollow sections” and “cold-formed hollow sections”.