Provided performance P354 floor vibration

Tekla Structural Designer
2021
Tekla Structural Designer

Provided performance P354 floor vibration

System frequency

Deflections

For the primary beam, the base maximum simply supported deflection, δPBSS, is derived from the analysis model with no allowance for boundary conditions.

For the secondary beam, the base maximum simply supported deflection, δSBSS, is derived from the analysis model and the maximum deflection for a fixed end condition, δSBFE, is calculated from,

δSBFE = m*b*LSB4 /(384*ES *ISB ) + m*b*LSB2 /(24*G*Ay )
Where
m = unit mass in kN/mm2
b = secondary beam spacing in mm
LSB = span of the secondary beam in mm
ISB = the inertia of the secondary beam in mm 4
ES = the steel modulus in kN/mm2
G = the steel shear modulus in kN/mm2
Ay = the major axis shear area in mm2

For the slab, the base maximum deflection for a fixed end condition, δSlabFE, is calculated from,

δSlabFE = m*LSlab 4/(384*EC *ISlab)
Where
m = unit mass in kN/mm 2
LSlab = span of the slab in mm
ISlab = the inertia of the slab in mm 4/mm
EC = the dynamic concrete slab modulus in kN/mm2
= Es *1.1/αshort

These base, maximum simply supported deflections for both primary and secondary beams, δ **SS, derived from the analysis model, can be adjusted to cater for boundary conditions for 'two-span continuous' or 'three-span continuous' cases to give δ barSS.

For 'two span continuous' the adjusted deflection is taken from P354 as,

δbarSS = MIN[(0.4 + kM /kS * (1 + 0.6 * LS 2/LM2 ))/(1 + kM /kS ), 1.0] * δ**SS
Where
kM = the 'stiffness' of the critical span selected by the user (primary or secondary beam as appropriate)
= IM /LM
kS = the stiffness of the adjoining span selected by the user (primary or secondary beam as appropriate)
= IS/LS
LM = the span of the critical span selected by the user (primary or secondary beam as appropriate)
LS = the span pf the adjoining span selected by the user (primary or secondary beam as appropriate)
IM = the inertia of the critical span selected by the user (primary or secondary beam as appropriate)
IS = the inertia of the adjoining span selected by the user (primary or secondary beam as appropriate)

For 'three span continuous' the adjusted deflection is taken from P354 as,

δbarSS = MIN[(0.6 + 2 * kM /k S * (1 + 1.2 * LS2 /LM2 ))/(3 + 2 * kM /k S ), 1.0] * δ**SS
Where
kM = the 'stiffness' of the critical (middle) span selected by the user (primary or secondary beam as appropriate)
= IM /LM
kS = the stiffness of the adjoining (outer) span selected by the user (primary or secondary beams as appropriate)
= IS /LS
LM = the span of the critical (middle) span selected by the user (primary or secondary beam as appropriate)
LS = the span of the adjoining (outer) span selected by the user (primary or secondary beams as appropriate)
IM = the inertia of the critical (middle) span selected by the user (primary or secondary beam as appropriate)
IS = the inertia of the adjoining (outer) span selected by the user (primary or secondary beams as appropriate)

Secondary Beam Mode

In this mode the primary beams form nodal lines (zero deflection) about which the secondary beams vibrate. The slab is assumed to be continuous over the secondary beams so a fixed end condition is used.

δSBmode = δ barSBSS + δ SlabFE
and
fSBmode = 18/ √ δ SBmode

Primary Beam Mode

In this mode the primary beams vibrate about the columns as simply supported beams whilst the secondary beams and slabs are taken to be fixed ended

δPBmode = δbarPBSS + δSBFE + δSlabFE
and
fPBmode = 18/ √ δPBmode

System Frequency

The natural frequency of the system, f0, is calculated from,

f0 = MIN{ fSBmode , fPBmode }

Limitations

The absolute minimum natural frequency of the floor system is limited to 3.0 Hz. Where the floor system frequency is below these limits the design fails.

Similarly, no single element within the floor structure should have a fundamental frequency less than 3.0 Hz. Three additional checks are therefore carried out and their results only published if there is a Fail. These checks are,

fPBSS =18/ √ δ PBSS must be ≥ 3 else the design Fails
fSBSS =18/ √ δ SBSS must be ≥ 3 else the design Fails
fSlabFE =18/ √ δSlabFE must be ≥ 3 else the design Fails

Modal mass

The 'modal mass' is the effective mass participating in the vibration of the floor. In accordance with SCI P354, it is taken as the 'unit mass' multiplied by the effective plan area of the floor participating in the motion as given by,

M = m * Leff * S
Where
m = the unit mass in kg/m2
Leff = the effective floor length
S = the effective floor width
Where
Leff = 09*(1.10)ny-1 *(E*ISB/(m*b*f02))0.25 but ≤ ny*Ly
Where
ny = number of bays ( ≤ 4) in the direction of the secondary beam span
EISB = dynamic flexural rigidity of the composite secondary beam (in Nm2 when m is in kg/m2)
b = floor beam spacing (in m)
f0 = system, natural frequency from above
Ly = span of the secondary beam (in m)
and
S = η*(1.15)nx-1 *( E*ISlab /(m* f02 ))0.25 but ≤ nx *Lx
Where
nx = number of bays ( ≤ 4) in the direction of the primary beam span
EISlab = dynamic flexural rigidity of the slab (in Nm2 when m is in kg/m2 ) system,
f0 = natural frequency from above
Lx = span of the primary beam (in m)

Where
η = frequency factor
= 0.5 for f0 < 5 Hz
= 21*f0 - 0.55 for 5 Hz ≤ f0 ≤ 6 Hz
= 0.71 for f0 > 6 Hz

Figure 1: Definition of variables used to establish effective modal mass

Mode Shape Factor

As previously described, there are two main mode shapes which relate to the lowest frequencies - a secondary beam mode and a primary beam mode. The lowest frequency of the two modes is used and the mode shape factors is determined using the same mode.

There are two mode shape factors, μe at the point of excitation and μr at the point of response.

If the response and excitation points are unknown, or if a general response for the whole floor is required, μe and μr can conservatively be taken as 1.

Tekla Structural Designer will not calculate the values of these mode shape factors, and will default to 1.0 but also gives you the option of providing values to be used.

Resonance Build-up Factor

The 'resonance build-up factor' makes an allowance for the time it takes for someone walking across the floor to begin to excite the floor - vibration is not instantaneous upon the first footfall. Hence, a 'walking time' is required and is calculated from the 'walking distance' (see:Maximum corridor length) divided by the 'walking velocity'.

First it is necessary to calculate the walking velocity as given by Equation 16 of SCI P354,

V = 67*fp2 - 4.83*fp + 4.5 for fp in the range 1.7 to 2.4 Hz
Where
fp = the pace (walking) frequency supplied by the user

The resonance build-up factor is taken from Equation 37 of SCI P354,

ρ = 1 - e (-2*π*ζ Lp*fp /V)
Where
ζ = the damping ratio
Lp = the walking distance
V = the walking velocity given above

Note that the resonance build-up factor has an upper bound of 1.0 and may, conservatively be set to 1.0.

Resonance Acceleration

Low Frequency Floors

For system frequencies between 3 Hz and 10 Hz, the root mean square (rms) acceleration is calculated from,

aw,rms = μe* μr* 0.1*Q*W*ρ/(2 * √2*M * ζ)

Where

μe & μr = mode shape factors
Q = the person's weight taken as 745.6 N (76 kg)
M = the modal mass (kg)
= the damping ratio
ρ = the resonance build-up factor
W = the appropriate code-defined weighting factor for the human perception of vibrations, based on the fundamental frequency, f 0
= f0 /5 for 2 ≤ f0 < 5
= 1.0 for 5 ≤ f0 ≤ 16
= 16/f0 for f0 > 16

High Frequency Floors

For system frequencies greater than 10 Hz, the root mean square (rms) acceleration is calculated from the following expression, which assumes that the floor exhibits a transient response,

aw,rms = 2*π* μ e* μ r * 185*Q*W /(M*f00.3*700* √2)

Response Factor

The 'base curves' in BS 6472: 1992 are given in terms of root mean square (rms) acceleration

The provided response factor is then calculated from,

Rprov = a w,rms /0.005

The 'required response factor', Rreqd, is a user input and leads to the final design condition,

Rprov R reqd

In SCI P354 the recommended Response Factors derive from BS 6472: 1992, where they are called 'Multiplying Factors' and are reproduced in SCI P354 as Tables 5.2 and 5.3.

Vibration Dose Values

When the floor has a higher than acceptable response factor, the acceptability of the floor may be assessed by considering the intermittent nature of the dynamic forces. This is accomplished by carrying out a Vibration Dose Value [VDV] analysis.

This method calculates the number of times an activity (for example walking along a corridor) will take place during an exposure period, na, from,

na = (1/Ta )*(VDV/(0.68*a w,rms ))4
where
Ta = the duration of the activity
= L p/V if L p is known OR
= value supplied by user if L p is not known
VDV = VDV value supplied by user, (default 0.4).

Typical VDV values are shown below:

Vibration dose limits (m/s1.75) for z-axis vibration specified by BS 6472
Place Low probability of adverse comment Adverse comment possible Adverse comment probable
buildings 16 h day 0.2 to 0.4 0.4 to 0.8 0.8 to 1.6
buildings 8 h night 0.13 0.26 0.51