Checks for limiting parameters (pile cap: ACI 318)

Tekla Structural Designer
2021
Tekla Structural Designer

Checks for limiting parameters (pile cap: ACI 318)

Limiting reinforcement parameters are specified in Design Options > Foundations > Isolated Foundations > Reinforcement Layout

Check for distance of pile cap overhang

The check passes if:

min ei
  >  
min (emin , emin,user)
where:
emin
  =  
MAX[230mm, 380mm - 0.5 * lp] when Rc ≤ 534 kN Metric
emin
  =  
MAX[9in, 15in - 0.5 * lp] when Rc ≤ 120 kips US Customary
emin
  =  
MAX[230mm, 530mm - 0.5 * lp] when 534 kN < Rc ≤ 1068 kN Metric
emin
  =  
MAX[9in, 21in - 0.5 * lp] when 120 kips < Rc ≤ 240 kips US Customary
emin
  =  
MAX[230mm, 685mm - 0.5 * lp] when 1068 kN < Rc ≤ 1779 kN Metric
emin
  =  
MAX[9in, 27in - 0.5 * lp] when 240 kips < Rc ≤ 400 kips US Customary
emin
  =  
MAX[230mm, 760mm - 0.5 * lp] when Rc > 1779 kN Metric
emin
  =  
MAX[9in, 30in - 0.5 * lp] when Rc > 400 kips US Customary
lp
  =  
least width/diameter of the pile

Check for minimum pile spacing

Check center to center spacing “s” between piles “i” and “j” in a pile group:

The check passes if:

If sij > min(smin , smin,user)

where

smin,user = user input

smin = max (least width of the pile + 0.6m , 0.9m) for metric units

smin = max (least width of the pile + 2ft. , 3 ft) for US customary units1

Check for maximum pile spacing

Check center to center maximum spacing “s” between piles “i” and “j” in a pile group:

The check passes if:

If sij < smax,user

smax,user = user input

Other checks

The remaining checks are identical to those for pad bases.

See: Pad Base and Strip Footing Design - Checks for limiting parameters (pad and strip base: ACI 318).

1 CRSI – Design handbook page 13-18