Design philosophy of P354 floor vibration

Tekla Structural Designer
2020
Tekla Structural Designer

Design philosophy of P354 floor vibration

General

The Engineer ensures the safety of building occupants by satisfying all design criteria at the Ultimate Limit State. Similarly, the health of building occupants is partly taken care of when deflection limits at the Serviceability Limit State are satisfied (although this Limit State does have other purposes than simply the health of occupants).

However, for floors that are subject to cyclic or sudden loading, it is the human perception of motion that could cause the performance of a floor to be found unsatisfactory. Such perception is usually related to acceleration levels. In most practical building structures, the reaction of the occupants to floor acceleration varies between irritation and a feeling of insecurity. This is based on the instinctive human perception that motion in a 'solid' building indicates inadequacy or imminent failure.

The working environment also affects the perception of motion. For busy environments, where the occupant is surrounded by the activity that is producing the vibrations, the perception of motion is reduced. In contrast, for quieter environments (such as laboratories and residential dwellings), where the source of vibration is unseen, the perception of motion is significantly heightened.

The design philosophy to ensure that the potential for such human response is minimized, has a number of facets,

  • the dynamic excitation causing the vibration i.e. the disturbing force profile, which is force and time dependent. For the sorts of building and occupancy considered here, this is the act of walking.
  • the required performance. This depends upon the type of environment. As discussed above this, in turn, depends upon the involvement of the occupant in the generation of the vibration and also on the nature of the occupancy. The latter is important for laboratories carrying out delicate work, or operating theatres, for example.
  • the provided performance. This is the "Response Factor" and is dependent on the system natural frequency and, more importantly, the participating mass. The latter is driven mainly by the selection of an area of floor that is reasonable and appropriate.

Dynamic excitation

In a classical spring-mass system that includes a (viscous) damper, when a simple force is applied to the mass to extend (or contract) the spring, the mass moves up and down (oscillates). This movement is significant at first but eventually reduces to zero due to the resistance offered by the damper. In a floor system in a building,

  • the mass is the self-weight of the floor and any other loading that is present for the majority of the time that the occupants could be exposed to vibration effects,
  • the spring is the stiffness of the floor system, which will have a number of different component beams (secondary and primary) and the floor slab,
  • the damper is provided by a number of elements that are able to absorb energy from the free vibration of the system. There will be energy absorbed,
    • within connections, since they behave 'better' than the ideal that is assumed
    • from losses due to the unsymmetrical nature of real buildings e.g. grid layout, and dispersion of loads from furnishings and contents
    • from components such as partitions that are out-of-plane of the vibration and interfere with the 'mode'.

The determination of the contribution of each of these components as they affect real floor systems is given in detail in later sections. These describe the 'response' side of the floor system. In order to establish the required performance of the system the 'input' must also be defined i.e. that event, events or continuum that is the 'dynamic excitation'.

In the simple example described at the start of this section the 'input' was simply a force that caused a displacement to the system and was then released. This might be equivalent to a person jumping off a chair onto the floor. However, in the context of the concerns over the vibration of floors, it is not this sort of input that is of interest. The main concern is the excitation of the floor brought about by walking.

Unlike the simple example, walking produces loading that is cyclic. This loading can be idealized into a series of sine curves of load against time. Each curve is an exact multiple of the walking frequency called harmonics. When one of these harmonics of the cyclic loading coincides with the natural frequency of the floor system then resonance is set up. The consequence of resonance that is detected, and may disturb occupants, is the associated peak acceleration. For the first harmonic, the peak acceleration is dependent upon the applied force (the weight of one standard person multiplied by a factor, αn), the mass of the system (the self-weight of the floor plate plus other loading that could be considered as permanent), and the amount of damping in the system (the damping ratio, ζ). The factor, αn, is known as a Fourier coefficient and links the magnitude of the applied force in any harmonic of the walking function to the weight of one standard person. It has been established experimentally for different activities and different activity frequencies.

Hence, the dynamic excitation of a floor is dependent upon the forcing function due to walking and its relationship to the natural frequency of the floor system. It is the level of the peak acceleration that this generates that is particularly important in determining the performance of the floor.

Required performance

The required performance of a floor system is very dependent upon the potential response of humans. Human response is a very complex subject since there is no such thing as a 'standard human'. The perception of vibration will differ from person to person, their body mass varies significantly and the body's reaction will depend upon age, gender etc. The human response has been studied and the accepted wisdom is embodied in BS 6472: 1992, Guide to evaluation of human exposure to vibration in buildings (1 Hz to 80 Hz) Ref. 1

It may be remembered that it is the acceleration of the floor system that the human perceives. BS 6472: 1992 provides a series of curves one of which is the 'base' limit of (vertical) acceleration against frequency (of the floor). Within the practical range of frequencies dealt with, a single value of the 'base' limit on acceleration is given as 0.005 m/s2. This single value holds

  • down to 3 Hz but no floor should be allowed to have a system natural frequency below this value anyway
  • up to 10 Hz. Such a large value would be unusual but beyond that point there is a simple linear relationship between the base limit of acceleration and the natural frequency within an extended but just practical range.

The accelerations acceptable for different use of buildings are described using the 'base' limits. Multiplying factors are used to increase the base acceleration limit according to the intended use of the building. The multiplying factors are referred to as 'response factors' in the SCI guidance. Thus the target acceleration of the floor under consideration is the root mean square acceleration multiplied by the response factor. This design condition is turned on its head to give a 'provided response factor' that is then compared with the 'required response factor'. The required response factor is the measure of the "Required performance" and is given in the SCI guidance as,

  • R = 8 for a workshop
  • R = 8 for a general office
  • R = 2 for a residential building during day time use

You should choose a required response factor based on both engineering judgement and the advice given in P354. In particular it may be noted that, "changing R by a factor of 2 is equivalent only to the most marginal change to human perception".

Provided performance

It is in establishing the provided performance that most of the design calculations are required. The object of these calculations is to determine the 'required response factor'.

The start point is the calculation of the natural frequency of the floor system. This is established from the individual component frequencies for each of two possible shape modes, namely the Secondary Beam Mode and the Primary Beam Mode. The natural frequencies of the individual components can be adjusted to allow for boundary conditions e.g. two spans continuous. The fundamental frequency, f0, is the lower value for the two modes considered. A minimum natural frequency is given in SCI P354 of 3.0 Hz.

Next the 'modal mass' is required. This is dependent upon the physical size of the floor plate selected and an effective width and/or length that is itself dependent on the natural frequency of the floor. The modal mass has by far the largest influence on the response factor provided.

The 'Resonance Build-up Factor' makes allowance for the time it takes for someone walking across the floor to begin to excite the floor - vibration is not instantaneous upon the first footfall. This has an upper limit of 1.0 and can be taken conservatively as 1.0. The calculation requires the 'damping ratio' - this is a user input.

The resonance build-up factor, the damping ratio, the modal mass, and the weight of a 'standard person' along with an appropriate Fourier coefficient are used to calculate the peak acceleration.

The final determination of the response factor provided requires the 'root mean square' acceleration. The rms acceleration has two formulations depending upon the fundamental, system frequency. The response factor is a very simple calculation.

The design condition is simply,

Rprov ≤ Rreqd