Why are wall wind zones reported as Zero when I review the Zone Loads for wind load cases?

Tekla Structural Designer 2026 - 2022 Zero Zone Loads wind zone wind
Environment
British Standard
Eurocode

Issue


Why are my wall wind zones reported as Zero?

 

Image
2017_03_30_12_08_321.png

Resolution


In the screenshot below, the Load ribbon > Wind Load group > Wind Wizard... command has defined the Ground level as  -0.5m. Wind is ignored below this value.

 

Image
2017_03_30_12_09_032.png




If we review the Model ribbon > Levels group > Construction Levels command, the levels in the screenshot below are between -6m and 0m.

 

Image
2017_03_30_12_09_463.png



The wind load is only applied beginning at the height of -0.5m as defined in the Wind Wizard.

Hence, the Zero locations are where the model falls below the Ground level of -0.5m where wind is ignored.

 